Golden Solar! Advance Power! Green Life!
● Efficient
Support over capacity ratio: 1.6X DC input overload.
High energy continuous output: 1.1X AC output overload.
The MPPT efficiency is up to 99.90%.
The lowest starting voltage can reach to 160V.
● Intelligent
Intelligent monitoring: one-stop intelligent operation and maintenance platform for users,
providing comprehensive and intuitive power station data monitoring.
Support RS485 / USB / WiFi / GPRS.
● Reliable
IP66
Input reverse wiring protection, AC short circuit protection, AC over current protection,
Input over voltage protection, Isolation protection, PV string detection, Anti-islanding protection,
Over temperature protection, Grounding fault monitoring, ZVRT, Anti-PID function, etc..
● Flexible
Intelligent IV scanning function: it can accurately locate the fault string and make the operation
and maintenance more efficient.
4 MPPT: more flexible string configuration and more choices for installation.
Remote maintenance: support online remote upgrade.
Fan drawer design: 1 minute quick fan replacement.
Model | MTG2-50K | MTG2-60K | MTG2-66K | MTG2-70K |
Input (DC) | ||||
Max. Input Power | 80KW | 96KW | 105.6KW | 112KW |
Max. Input Voltage | 1100V | |||
Start Voltage / Min. Operation Voltage | 250/180V | |||
MPPT Voltage Range | 200~1000V | |||
Number of MPP Trackers / String per MPPT | 3/2/3/2 | 3/3/3/3 | ||
Max. Current per MPPT | 39A/26A/39A/26A | 39A/39A/39A/39A | ||
Output (AC) | ||||
Rated Output Power | 50KW | 60KW | 66KW | 70KW |
Max. Output Current | 80.5A | 96.6A | 88.2A | 93.6A |
Max. Output Power | 55.5KVA | 66.6KVA | 73.3KVA | 77.7KVA |
Rated Grid Frequency | 50Hz / 60Hz | |||
Rated Grid Voltage | 230V /400V | 230V /400V | 277V /480V | 277V /480V |
Power Factor | - 0.8 ~ +0.8 (adjustable) | |||
THDI | < 3% (at rated power) | |||
Efficiency | ||||
Max. Efficiency | 98.60% | |||
Euro. Efficiency | 98.40% | |||
MPPT Efficiency | 99.90% | |||
Protection | ||||
Porotection | DC switch, Input reverse wiring protection, AC short circuit protetion, AC over current protection, Input over voltage protection, Isolation protection, PV string detection, Anti-islanding protection, Over temperature protection, Grounding fault monitoring, ZVRT, Anti-PID function, etc. | |||
Communication | ||||
Display | LED / LCD / WiFi+App | |||
Communication | Standard: RS485; Optional: WiFi / GPRS200 / Ethernet | |||
Standard Compliance | ||||
Grid Connection Standards | IEC 61727, IEC 62116, IEC 60068, IEC 61683, VDE-AR-N 4110:2018, VDE-AR-N 4105:2018, VDE-AR-N 4120:2018, EN 50549, AS/NZS 4777.2:2015, CEI 0-21, VDE 0126-1-1/A1 VFR 2014, UTE C15-712-1:2013, DEWA DRRG, NRS 097-2-1, MEA/PEA, C10/11, G98/G99 | |||
Safety / EMC | IEC 62109-1:2010, IEC 62109-2:2011, EN 61000-6-2:2005, EN 61000-6-3:2007/A1:2011 | |||
General Data | ||||
Dimension (W*H*D) | 650*440*260mm | |||
Weight | ≤50KG | |||
Operating Temperature Range | -25~+60℃ (Derating above 45℃) | |||
Cooling Method | Smart cooling | |||
Protection Degree | IP66 | |||
Noise | <50dB | |||
Max. Operating Altitude | 4000m (Derating above 2000m) | |||
Relative Humidity | 0~100% | |||
Consumption at Night | < 1W | |||
Topology | Transformerless | |||
Warranty | 5 years (standard) / 10 years (optional) |